1. Ensure the reliability of power supply Adopting two-phase incomplete star can ensure that when single-phase grounding occurs in the small grounding power grid, only Remove one line, and the other line can run with faults. Ensure the reliability of power supply. The neutral point ungrounded small current grounding system is also the neutral point ungrounded system.
2. In the small current grounding system, the installation of 2 current transformers (stipulated in phases A and C) can meet the requirements of protection and measurement devices, and there is no need to install current transformers in each phase of the three phase.
3. When the small current grounding system is grounded at two points. Small current grounding system allowsXu single phase-to-phase operation for one to two hours. When two points of different lines are grounded, the three-phase complete star-shaped wiring 100% removes two lines, and the power outage range is large; two-phase incomplete star-shaped wiring has a two-thirds of the chance to remove one line, and the power outage range is small and the reliability is high.
4. Two-phase incomplete star-shaped wiring form. ( Post-transmission) x0dx0a is the most used in actual work. It saves a current transformer and uses the synthetic currents of phases A and C to form a reverse phase B-phase current.
5. The two-line transformers are installed in different phases (for example, the 1st line B phase is not installed, and the 2nd line C phase is not installed). In a total of 6 kinds of two-point grounding short circuits (A1BA1CB1AB1CC1AC1B2), when only the two-line transformer phase two-point grounding short circuit (B1C2), the two The line does not work.So it is 1/6.
The analysis is as follows: high-current grounding and small-current grounding are both grounded by neutral points in the power system, and they are distinguished according to the main operating characteristics. The small grounding current system is also known as the ineffective grounding system. Including neutral point non-grounding, extinguishing arc coil grounding, and high-impedance grounding system.
When a single-phase grounding fault occurs in a neutral point direct grounding system (including a system grounded by a small impedance), the grounding short-circuit current is very large, so this system is called a high-current grounding system. It adopts a system that is not grounded at the neutral point or grounded by an arc coil.
The system voltage level is 110KV and above, and the neutral point direct grounding system is called high-current grounding system.The system voltage level is 35KV and below, and the neutral point is not grounded or compensated with an arc extinguishing coil is called a small current grounding system.
For the grounding of primary equipment, there are mainly direct grounding, resistance grounding, and extinguishing arc coil grounding. In a system above 220kV, the neutral point of the main transformer is directly grounded, which is called a high-current grounding system. In the 110 and 66kv systems, the neutral point arc coil of the main transformer is more grounded, which is called the small current grounding system.
Small current grounding system refers to a system that uses neutral point non-grounding or grounding through arc coils.
In a system with direct grounding at a neutral point, when a single-phase grounding fault occurs, the grounding short-circuit current is large. This system is called a high-current grounding system. Generally, the system of 110kv and above adopts a high-current grounding system.
Small current grounding system includes: neutral point non-grounding system, neutral point through arc coil grounding system, neutral point through large resistance grounding system. ( Neutral point ineffective grounding system), the grounding current is relatively small when a failure occurs.
The characteristic of a small grounding current is that when a one-phase grounding fault occurs, the grounding current is limited to a smaller value, and the steady-state voltage of the non-fault phase may reach the line voltage. The large grounding current system is also known as the effective grounding system. Including neutral point direct grounding and low-impedance grounding systems.
In China, the classification criteria: the system of X0/X14 to 5 belongs to the small grounding current system (the system of X0/X13 in the United States and Western Europe belongs to the small grounding current system), of which: X0 is the zero-sequence reactor of the system, and X1 is the positive sequence reactor of the system. Note: X0 is the zero-sequence reactor of the system, and X1 is the positive sequence reactor of the system.
Large grounding current system - a three-phase system that is directly grounded at the grounding power system. When a single-phase grounding failure occurs, the grounding short-circuit current is very large, so it is called a large grounding current system. Generally, 110kV and above systems or 380/220V three-phase four-wire systems.
The system voltage level is 110KV and above, and the neutral point direct grounding system is called high-current grounding system. The system voltage level is 35KV and below, and the neutral point is not grounded or compensated with an arc extinguishing coil is called a small current grounding system.
When a single-phase grounding fault occurs in a neutral point direct grounding system (including a system grounded by a small impedance), the grounding short-circuit current is very large, so this system is called a high-current grounding system. It adopts a system that is not grounded at the neutral point or grounded by an arc coil.
High-current grounding and small-current grounding are both grounded by neutral points in the power system, which are distinguished according to the main operating characteristics. The small grounding current system is also known as the ineffective grounding system. Including neutral point non-grounding, extinguishing arc coil grounding, and high-impedance grounding system.
In a system where the neutral point is directly grounded, when a single-phase grounding fault occurs, the grounding short-circuit current is very large. This system is called a high-current grounding system. Generally, the system of 110kv and above adopts a high-current grounding system.
1. The characteristic of a small grounding current is that when a one-phase grounding fault occurs, the grounding current is limited to a smaller value, and the steady-state voltage of the non-fault phase may reach the line voltage. The large grounding current system is also known as the effective grounding system. Including neutral point direct grounding and low-impedance grounding systems.
2. In the neutral point ungrounded system, when the insulation of any phase is destroyed and grounded, the line voltage between the phases remains unchanged and can continue to operate with faults, while the ground voltage and the ground capacitance current of each point change, and the point of the neutral point is far from the earth potential.
3. The neutral point is not grounded, and the earth and the system are not electrically connected.
4. When one-phase grounding occurs in the small current grounding system, the grounding relative voltage is zero, and the relative ground voltage of the other two is increased by three times. The magnitude of the grounding current at the contact point is equal to the sum of the grounding capacitance current of all lines.
5. When a one-phase metallic grounding occurs in a small-current grounding system, the ground relative voltage is zero, and the non-ground relative ground voltage rises to line voltage.
Customizable export data queries-APP, download it now, new users will receive a novice gift pack.
1. Ensure the reliability of power supply Adopting two-phase incomplete star can ensure that when single-phase grounding occurs in the small grounding power grid, only Remove one line, and the other line can run with faults. Ensure the reliability of power supply. The neutral point ungrounded small current grounding system is also the neutral point ungrounded system.
2. In the small current grounding system, the installation of 2 current transformers (stipulated in phases A and C) can meet the requirements of protection and measurement devices, and there is no need to install current transformers in each phase of the three phase.
3. When the small current grounding system is grounded at two points. Small current grounding system allowsXu single phase-to-phase operation for one to two hours. When two points of different lines are grounded, the three-phase complete star-shaped wiring 100% removes two lines, and the power outage range is large; two-phase incomplete star-shaped wiring has a two-thirds of the chance to remove one line, and the power outage range is small and the reliability is high.
4. Two-phase incomplete star-shaped wiring form. ( Post-transmission) x0dx0a is the most used in actual work. It saves a current transformer and uses the synthetic currents of phases A and C to form a reverse phase B-phase current.
5. The two-line transformers are installed in different phases (for example, the 1st line B phase is not installed, and the 2nd line C phase is not installed). In a total of 6 kinds of two-point grounding short circuits (A1BA1CB1AB1CC1AC1B2), when only the two-line transformer phase two-point grounding short circuit (B1C2), the two The line does not work.So it is 1/6.
The analysis is as follows: high-current grounding and small-current grounding are both grounded by neutral points in the power system, and they are distinguished according to the main operating characteristics. The small grounding current system is also known as the ineffective grounding system. Including neutral point non-grounding, extinguishing arc coil grounding, and high-impedance grounding system.
When a single-phase grounding fault occurs in a neutral point direct grounding system (including a system grounded by a small impedance), the grounding short-circuit current is very large, so this system is called a high-current grounding system. It adopts a system that is not grounded at the neutral point or grounded by an arc coil.
The system voltage level is 110KV and above, and the neutral point direct grounding system is called high-current grounding system.The system voltage level is 35KV and below, and the neutral point is not grounded or compensated with an arc extinguishing coil is called a small current grounding system.
For the grounding of primary equipment, there are mainly direct grounding, resistance grounding, and extinguishing arc coil grounding. In a system above 220kV, the neutral point of the main transformer is directly grounded, which is called a high-current grounding system. In the 110 and 66kv systems, the neutral point arc coil of the main transformer is more grounded, which is called the small current grounding system.
Small current grounding system refers to a system that uses neutral point non-grounding or grounding through arc coils.
In a system with direct grounding at a neutral point, when a single-phase grounding fault occurs, the grounding short-circuit current is large. This system is called a high-current grounding system. Generally, the system of 110kv and above adopts a high-current grounding system.
Small current grounding system includes: neutral point non-grounding system, neutral point through arc coil grounding system, neutral point through large resistance grounding system. ( Neutral point ineffective grounding system), the grounding current is relatively small when a failure occurs.
The characteristic of a small grounding current is that when a one-phase grounding fault occurs, the grounding current is limited to a smaller value, and the steady-state voltage of the non-fault phase may reach the line voltage. The large grounding current system is also known as the effective grounding system. Including neutral point direct grounding and low-impedance grounding systems.
In China, the classification criteria: the system of X0/X14 to 5 belongs to the small grounding current system (the system of X0/X13 in the United States and Western Europe belongs to the small grounding current system), of which: X0 is the zero-sequence reactor of the system, and X1 is the positive sequence reactor of the system. Note: X0 is the zero-sequence reactor of the system, and X1 is the positive sequence reactor of the system.
Large grounding current system - a three-phase system that is directly grounded at the grounding power system. When a single-phase grounding failure occurs, the grounding short-circuit current is very large, so it is called a large grounding current system. Generally, 110kV and above systems or 380/220V three-phase four-wire systems.
The system voltage level is 110KV and above, and the neutral point direct grounding system is called high-current grounding system. The system voltage level is 35KV and below, and the neutral point is not grounded or compensated with an arc extinguishing coil is called a small current grounding system.
When a single-phase grounding fault occurs in a neutral point direct grounding system (including a system grounded by a small impedance), the grounding short-circuit current is very large, so this system is called a high-current grounding system. It adopts a system that is not grounded at the neutral point or grounded by an arc coil.
High-current grounding and small-current grounding are both grounded by neutral points in the power system, which are distinguished according to the main operating characteristics. The small grounding current system is also known as the ineffective grounding system. Including neutral point non-grounding, extinguishing arc coil grounding, and high-impedance grounding system.
In a system where the neutral point is directly grounded, when a single-phase grounding fault occurs, the grounding short-circuit current is very large. This system is called a high-current grounding system. Generally, the system of 110kv and above adopts a high-current grounding system.
1. The characteristic of a small grounding current is that when a one-phase grounding fault occurs, the grounding current is limited to a smaller value, and the steady-state voltage of the non-fault phase may reach the line voltage. The large grounding current system is also known as the effective grounding system. Including neutral point direct grounding and low-impedance grounding systems.
2. In the neutral point ungrounded system, when the insulation of any phase is destroyed and grounded, the line voltage between the phases remains unchanged and can continue to operate with faults, while the ground voltage and the ground capacitance current of each point change, and the point of the neutral point is far from the earth potential.
3. The neutral point is not grounded, and the earth and the system are not electrically connected.
4. When one-phase grounding occurs in the small current grounding system, the grounding relative voltage is zero, and the relative ground voltage of the other two is increased by three times. The magnitude of the grounding current at the contact point is equal to the sum of the grounding capacitance current of all lines.
5. When a one-phase metallic grounding occurs in a small-current grounding system, the ground relative voltage is zero, and the non-ground relative ground voltage rises to line voltage.
How to track multiple supply chain tiers
author: 2024-12-24 01:11Global trade corridor analysis
author: 2024-12-24 01:00Dairy products HS code verification
author: 2024-12-24 00:20HS code indexing for procurement catalogs
author: 2024-12-23 23:56Rubber exports HS code classification
author: 2024-12-23 23:46How to use trade data for market expansion
author: 2024-12-24 01:51Supplier relationship management with trade data
author: 2024-12-24 01:16Regional value content by HS code
author: 2024-12-24 00:18HS code integration with supply chain
author: 2024-12-23 23:37137.98MB
Check691.91MB
Check991.44MB
Check492.46MB
Check666.29MB
Check156.75MB
Check174.86MB
Check963.11MB
Check398.44MB
Check341.82MB
Check977.72MB
Check543.84MB
Check682.66MB
Check327.35MB
Check392.43MB
Check182.97MB
Check263.54MB
Check352.16MB
Check414.46MB
Check718.38MB
Check437.61MB
Check382.45MB
Check224.61MB
Check679.97MB
Check628.75MB
Check847.78MB
Check372.54MB
Check645.58MB
Check313.47MB
Check581.71MB
Check268.99MB
Check311.63MB
Check495.89MB
Check555.37MB
Check654.54MB
Check978.81MB
CheckScan to install
Customizable export data queries to discover more
Netizen comments More
1267 How to facilitate cross-border returns
2024-12-24 01:28 recommend
238 Shipping lane performance metrics
2024-12-24 01:25 recommend
2467 How to reduce compliance-related delays
2024-12-24 00:48 recommend
1481 Advanced shipment lead time analysis
2024-12-24 00:38 recommend
1689 How to manage trade credit risks
2024-12-23 23:57 recommend